Reactive Power Capacitor Compensation-2(Measured power factor)

1. calculate and confirm the power factor :

Reactive Power Capacitor Compensation-2(Measured power factor)(Formula 1)

Where:

— Calculated active power of the enterprise

— Calculated reactive power of the enterprise

, — Annual average active and reactive load coefficients, with ranging from 0.7 to 0.75, and taken as 0.76.

After artificial compensation, the maximum calculated load power factor should be above 0.9.

For enterprises already in production, the method for determining the average power factor is as follows:

Reactive Power Capacitor Compensation-2(Measured power factor)(Formula 2)

Where:

— Monthly active energy consumption, i.e., the reading of the active energy meter (kWh)

— Monthly reactive energy consumption, i.e., the reading of the reactive energy meter (kvarh)

Once the power factor is known, the capacitor capacity can be determined.

Reactive Power Capacitor Compensation-2(Measured power factor)(Formula 3)

The power factor after compensation is:

Reactive Power Capacitor Compensation-2(Measured power factor)(Formula 4)

During the calculation of Equation (Formula 4), the relationship between and can be derived from trigonometry:

 

Reactive Power Capacitor Compensation-2(Measured power factor)(Formula 5)