+8613916759436winzpower@winzele.com
480V 60Hz 3 phase voltage stabilizer 1000KVA
  • 480V 60Hz 3 phase voltage stabilizer 1000KVA
  • 480V 60Hz 3 phase voltage stabilizer 1000KVA
  • 480V 60Hz 3 phase voltage stabilizer 1000KVA
  • 480V 60Hz 3 phase voltage stabilizer 1000KVA
  • 480V 60Hz 3 phase voltage stabilizer 1000KVA

480V 60Hz 3 phase voltage stabilizer 1000KVA

Product Details

Product Introduction

The following countries and regions primarily use 480V, 60Hz three-phase power grids:
The United States, Canada, Mexico, Brazil, Costa Rica, and Guyana.
The 480V, 60Hz AC voltage stabilizer is used to stabilize the 480V/60Hz voltage system.
This 1000KVA three-phase voltage stabilizer features three-phase split-phase regulation and automatic voltage balancing.
The voltage stabilizer capacity matches the 630K to 1250K transformer range for overall voltage regulation.
Due to the large capacity of the voltage stabilizer, three independent cabinets (L1, L2, and L3) are used.
This is also a servo-type AC voltage stabilizer.

Technical Parameters

INPUT
Type SBW-F-1000KVA[480V] Three-phase voltage automatic balancing type
Power Rating(KVA) 1000KVA
Voltage Range(VAC) 384V~576V
Frequency(Hz) 50/60Hz
Phases  3 Phases  5 Wires
Current(A) 1202A
OUTPUT
Power Rating(KVA) 1000KVA
Current Rating(A) 1202A
Output Voltage(V) 480VAC
Output Precision 480VAC±1~5% (Adjustable) Default Setting±2%
Frequency  50Hz/60Hz
Efficiency 98.8%
Wave(THD increment) Compared with the input  waveform, the increment of the THD output  is not more than 0.1%
Overload Capacity In the overload 1.5 times the duration of not less than 5 minutes
Stabilization Time  The input voltage ratings relative to the Range change of 10%, stable time less than 1 Seconds
Safety performance
Isolation Resistance ≥2MΩ
Withstand voltage 2500V
Protection function
Over-Voltage The output phase voltage is more than 10%, and the output is cut off
Under-voltage The output phase voltage is less than 10%, and the output is cut off
Phase fault Lack phase detection
Over-Loading When the system is overloaded, the output is cut off, and the time delay can be set
Over-Current When the system is overcurrent, the output is cut off.MCCB Protection
Short-Circuit When the system is short circuit, the output is cut off.MCCB Protection
Bypass Manual Bypass
Phase-Sequence Phase sequence relay
Display
Display media Display Panel Multi function LCD segment code OR Touchscreen 7”
Voltage
Input and output voltage, true RMS value calculation LCD display
Current Input Current, true RMS value calculation LCD display
Fault Status Fault status display OV UV OL etc
Other features
Communication RS485 Modbus RTU
Working Temperature -15℃+55℃
Relative Humidity 10%-90%(20℃±5℃)
Altitude <2000m
Noise Level(dB)  <55dB

Application

This product is designed for voltage regulation in 480V power supply environments and is suitable for three-phase industrial and commercial environments. Its 1000KVA capacity is primarily used for overall voltage regulation in hospitals, high-power chemical equipment, independent workshops, and factory distribution rooms. It effectively improves power supply quality and ensures the safe and stable operation of various equipment.

Product Photos

 

 

 

 

Send Inquiry